Single-snapshot post-OPF operability study
<!– study-executable –>
Audience: power-system researchers · Scope: one solved native-static equilibrium, with optional finite stress and load-model comparisons.
This tutorial shows how to turn one SI-valued OPF/PF solution into a compact, auditable operability record. The workflow is deliberately snapshot-first: contingencies and operating envelopes are not implied. If several cases are available, evaluate each case independently and attach the case label outside the processor.
The repository includes a runnable companion study at scripts/run_post_opf_operability_study.jl. It builds a small balanced four-wire feeder, evaluates constant-power and ZIP load models, and prints the snapshot rows plus finite stress summaries. It also includes an unbalanced DELTA case and a floating-neutral WYE case so the connection-level voltage, sequence, and neutral-displacement evidence are exercised. A final single-phase transformer case checks a separate low-voltage zone and its local voltage bounds:
julia --project=. scripts/run_post_opf_operability_study.jlThe script asserts that all declared snapshots and finite rows pass. Its final PASS line means only that this finite, declared study completed; it is not a global solvability or operating-envelope claim.
From a checkout with pinned dependencies installed, run julia --project=. scripts/run_study_tutorials.jl, or paste this page's Julia blocks into a fresh session in order. CI executes the published blocks on Julia 1.10 and current stable.
Build the teaching feeder
The data are synthetic: a 230 V source supplies a 2 kW constant-power load through phase and neutral conductors of 0.05 Ω each. Only the source neutral is grounded. This single-phase example keeps the reference calculation simple while retaining neutral displacement.
using PowerOptLab
using BMOPFTools: parse_bmopf, solve_pf, SIUnitsScaling
function resistive_feeder(; power_w=2000.0, model="constant_power")
parse_bmopf("""
{"bus": {
"grid": {"terminal_names": ["1", "n"],
"perfectly_grounded_terminals": ["n"]},
"loadbus": {"terminal_names": ["1", "n"]}},
"voltage_source": {
"supply": {"bus": "grid", "terminal_map": ["1"],
"v_magnitude": [230.0], "v_angle": [0.0]}},
"linecode": {"cable": {"R_series_1_1": 0.05, "R_series_2_2": 0.05}},
"line": {"service": {"bus_from": "grid", "bus_to": "loadbus",
"terminal_map_from": ["1", "n"], "terminal_map_to": ["1", "n"],
"linecode": "cable", "length": 1.0}},
"load": {"demand": {"bus": "loadbus", "terminal_map": ["1", "n"],
"configuration": "SINGLE_PHASE", "model": "$model",
"p_nom": [$power_w], "q_nom": [0.0], "v_nom": [230.0]}}}
"""; from_string=true)
end
net = resistive_feeder()
vbase = 230.0
loop_resistance = 0.10
load_voltage_ref = (vbase + sqrt(vbase^2 - 4loop_resistance*2000.0))/2
neutral_voltage_ref = (vbase - load_voltage_ref)/2The high-voltage root of $U^2-230U+0.10P=0$ gives approximately 229.127 V phase-to-neutral at the load and 0.4364 V neutral-to-earth. This independent reference is conditional on the resistive, unity-power-factor circuit.
1. Define the claim before running the checker
check_opf_operability separates several claims that are often conflated:
| Claim | Evidence | Typical status |
|---|---|---|
| The reported point satisfies the audited static equations | endpoint residual and domain checks | :pass or :fail |
| Declared voltage or VUF limits hold | terminal and sequence checks | :pass or :fail |
| The local equilibrium is regular | scaled Jacobian and critical mode | :pass or :inconclusive |
| The point is connected to the energized no-load branch | HELM or continuation evidence | :pass or :inconclusive |
| A sufficient local uniqueness region contains the point | fixed-point certificate | :pass or :inconclusive |
The aggregate result is not a hidden stability verdict. A certificate or reachability failure is conservative evidence, not proof of non-existence or dynamic voltage instability.
2. Audit one solved point
For a workflow that may receive heterogeneous network dictionaries, run the cheap scope audit before solving. It distinguishes native frozen-dispatch readiness from an unsupported control seam and catches missing or dangling voltage-source references without treating them as infeasibility:
scope = operability_scope_audit(net)
scope["status"]
scope["topology"]
scope["unsupported_reasons"]
@assert scope["status"] == :supportedThe checker consumes the SI-valued solution returned by BMOPFTools. Pass the audited scaling policy explicitly when the solution is detached from its OPF context. For a non-SI policy, provide voltage and current bases for every bus; the checker rejects incomplete base maps rather than inventing defaults.
using BMOPFTools: solve_pf, SIUnitsScaling
using PowerOptLab
pf = solve_pf(net; per_unit=false)
@assert pf["termination_status"] in ("LOCALLY_SOLVED", "OPTIMAL")
spec = OperabilitySpec(
scaling_policy = SIUnitsScaling(),
voltage_min = 0.95 * vbase,
voltage_max = 1.05 * vbase,
vuf_max = 0.02,
compute_helm = true,
compute_fixed_point_certificate = true,
)
report = check_opf_operability(net, pf; spec)
report.status
@assert report.status == :passThe detailed result keeps the ordering and physical interpretation needed for research review:
report.checks["endpoint"]
report.checks["terminal_voltage_bounds"]
report.checks["sequence_unbalance"]
report.branch_evidence["dP_dV"]
report.branch_evidence["critical_mode"]
report.branch_evidence["reachability"]
report.branch_evidence["fixed_point_certificate"]
report.provenance["operability"]["model_inventory"]The dP_dV records distinguish requested from realized power and retain the path-qualified sign convention. Positive- and negative-sequence derivatives are complementary summaries; they must not replace phase- or connection-level evidence in an unbalanced system.
3. Produce a study-table row
Use operability_snapshot_row when the study needs one deterministic row per case. It includes endpoint and conditioning evidence, voltage/VUF extrema, branch-indicator counts, HELM/certificate statuses, and unsupported-scope counts. It is intentionally not a contingency or envelope row.
row = operability_snapshot_row(report; snapshot_id="base")
@assert row.status == :pass
@assert row.endpoint_status == :pass
@assert abs(row.minimum_terminal_voltage - load_voltage_ref) < 1e-4
@assert row.maximum_vuf_status == :not_applicable
println("Operability: ", row.status, "; minimum voltage = ",
round(row.minimum_terminal_voltage; digits=4), " V")
row.status
row.schema_version
row.claim_scope
row.minimum_terminal_voltage
row.maximum_vuf
row.maximum_vuf_status # :not_applicable when no complete 3-phase bus exists
row.maximum_abs_terminal_angle_derivative # `missing` when unavailable
row.sequence_sensitivity_status
row.maximum_abs_positive_sequence_magnitude_derivative # `missing` when unavailable
row.maximum_abs_negative_sequence_magnitude_derivative # `missing` when unavailable
row.maximum_abs_vuf_derivative # `missing` when unavailable
row.endpoint_status
row.model_domain_status
row.jacobian_regular_status
row.jacobian_step_validation_status
row.analytic_jacobian_validation_status
row.analytic_load_scale_rhs_validation_status
row.terminal_voltage_bounds_status
row.sequence_unbalance_status
row.high_side_indicator_count
row.near_nose_indicator_count
row.fixed_point_certificate_status
row.fixed_point_condition_margin # best finite-scan robustness margin
row.fixed_point_radius_condition_margin # selected-radius containment margin
row.scope_status
row.upstream_adapter_version
row.upstream_adapter_fingerprint
row.upstream_public_equilibrium_seam
row.closure
row.control_closure
row.topology_has_voltage_source
row.unsupported_reasons
row.helm_reachability_status
row.scope # "single_snapshot_static_ybus"For reproducibility, retain the upstream seam record alongside the rows:
operability_upstream_audit()
report.provenance["operability"]["upstream"]The record's compatibility_status should be :supported before pooling native snapshot rows.
For a collection of already solved cases, map the stable checker over the cases and retain the case identifier in snapshot_id:
half_load = resistive_feeder(power_w=1000.0)
solved_cases = [(id="base", network=net, solution=pf),
(id="half_load", network=half_load,
solution=solve_pf(half_load; per_unit=false))]
rows = [
operability_snapshot_row(
check_opf_operability(case.network, case.solution; spec),
snapshot_id = case.id,
)
for case in solved_cases
]
@assert all(row.status == :pass for row in rows)This is the appropriate place to add a contingency label later. The processor itself still evaluates one network/solution pair at a time.
4. Add finite, declared stress directions
Stress campaigns are useful for sensitivity studies, but their evidence is finite and path-specific. Supply the solve callback explicitly and keep the same checker specification for each point:
directions = [
OperabilityStressDirection(:uniform),
OperabilityStressDirection(:reactive_removed;
p_scale=1.0, q_scale=0.0),
]
stress_rows = operability_stress_rows(net, pf;
spec = OperabilitySpec(
scaling_policy = SIUnitsScaling(),
compute_fixed_point_certificate = true,
),
directions = directions,
lambdas = [0.0, 0.5, 1.0],
solve = network -> solve_pf(network; per_unit=false),
)
stress_summary = operability_stress_summary(stress_rows)
@assert length(stress_rows) == 6
@assert all(row.status == :pass for row in stress_rows)
@assert all(row.boundary_status == :not_observed for row in stress_summary)
println("Operability stress study: ", length(stress_rows), " finite passing rows")Each row retains the direction, loading parameter, endpoint status, certificate status, the best finite-scan contraction margin, and any solve/checking error. A missing non-pass boundary is reported as :not_observed; it is not an unlimited margin.
For load-law uncertainty, label each finite campaign and combine the rows with operability_stress_ensemble_rows:
alternative_net = resistive_feeder(model="constant_current")
alternative_pf = solve_pf(alternative_net; per_unit=false)
alternative_rows = operability_stress_rows(alternative_net, alternative_pf;
spec=OperabilitySpec(scaling_policy=SIUnitsScaling(),
compute_fixed_point_certificate=true),
directions=directions, lambdas=[0.0, 0.5, 1.0],
solve=network -> solve_pf(network; per_unit=false))
@assert all(row.status == :pass for row in alternative_rows)
ensemble = operability_stress_ensemble_rows(Dict(
"nominal" => stress_rows,
"alternative_load_model" => alternative_rows,
))
@assert all(row.status == :pass for row in ensemble)The resulting table supports comparisons across declared models. It does not promote a finite ensemble into a global operating envelope.
5. Interpret unsupported scope explicitly
The current residual scope is the native static ybus_linearized model: constant-P/I/Z, ZIP, and finite exponential loads with supported WYE, SINGLEPHASE, and DELTA connections. Generators, IBR controls, unsupported load laws, and unsupported connections are returned as `:notapplicable` with reasons in the report and its provenance. A missing source reference is also reported as unsupported, as the deliberately incomplete network below shows:
unsupported_net = deepcopy(net)
delete!(unsupported_net, "voltage_source") # No prescribed voltage reference.
unsupported_report = check_opf_operability(unsupported_net, pf; spec=spec)
@assert unsupported_report.status == :not_applicable
@assert !isempty(unsupported_report.unsupported)
unsupported_report.status
unsupported_report.unsupported
unsupported_report.checks["scope"]
unsupported_report.provenance["operability"]Do not reinterpret :not_applicable as a pass or a failed power-flow solve. It means that the requested claim lies outside this processor's declared equation seam.
6. Minimum publication record
For each snapshot, retain:
- the network/model identifier and the SI-valued solution provenance;
- the scaling policy and complete coordinate bases when non-SI coordinates were used;
- residual tolerances, voltage/VUF limits, and closure (
:frozen_dispatchin the current native slice); - the snapshot row plus detailed
dP_dV, sequence, Jacobian, and certificate evidence when those checks were requested; and - any finite stress direction, lambda grid, solver callback version, and non-pass boundary observed.
This record makes the positive claim auditable without implying contingency coverage, global branch discovery, or dynamic voltage stability.
See Post-OPF operability for the full result contract, equations, certificate interpretation and supported study scope.