HELM power flow
Kind: Bespoke algorithm · Maturity: prototype · Direction: forward · Temporal: single-snapshot
PowerOptLab adds a deterministic, non-iterative multiconductor (4-wire and beyond) power-flow solver based on the Holomorphic Embedding Load-flow Method (HELM): solve_pf_helm (standard result dictionary) and helm_series (programmatic HelmResult). It is a bespoke algorithm — a new solution method built on the BMOPFTools engine's public admittance-matrix API — and complements the engine's Ipopt-based solve_pf: no initial guess and no convergence tuning. It reports physical mismatch, Padé spread, and coefficient-tail diagnostics; finite-order divergence is deliberately not presented as a proof that no power-flow solution exists.
res = solve_pf_helm(net)
res["termination_status"] # "HELM_CONVERGED" | "HELM_SERIES_DIVERGED" | "HELM_MAX_ORDER"
res["bus"]["lb"]["a"]["vm"] # voltage magnitude (V)
res["helm"]["pade_spread"] # last-two Padé differences, one per series row
res["helm"]["singularity_estimate"] # heuristic Domb–Sykes diagnosticThe augmented (bordered) admittance matrix
Ideal elements — a closed switch, a zero-leakage transformer — have no finite admittance: stamping a huge 1/z corrupts conditioning, and a singular zero-leakage block loses the coupling entirely. The engine's ybus_augmented extends the passive Ybus with one constraint row and auxiliary current unknown per winding port or ideal coupling:
\[\mathbf{K} = \begin{bmatrix} \mathbf{Y} & \mathbf{A}^{\mathsf T} \\ \mathbf{A} & -\mathbf{D} \end{bmatrix}, \qquad \mathbf{K} \begin{bmatrix} \mathbf{V} \\ \mathbf{w} \end{bmatrix} = \begin{bmatrix} \mathbf{I}_{\text{inj}} \\ \mathbf{0} \end{bmatrix}\]
Each IdealCoupling describes a row of $\mathbf{A}$. With conditioning scale $y_0$, physical current $i=y_0w$, and winding incidence $C$, $A=y_0C$ and $D=y_0^2Z$. Thus the port law is $CV=Zi$. The full leakage block can be nonzero and coupled; HELM preserves it in the germ, every series solve, and the final residual.
- Closed switches impose $V_{\text{from}}-V_{\text{to}}=0$ when
switches=:constrain; the default:aliasfuses their nodes. - Zero-leakage winding cores impose exact coil-voltage ratios. Small finite leakage is retained, including at the representation threshold.
- Supported transformer subtypes are
single_phase,wye_delta,delta_wye,single_phase_autotransformer,open_delta_regulator,center_tapandn_winding, within the upstream API's validated domains. - Unity-ratio isolated transformers still use winding equations. They do not fuse neutral references (the upstream
PSK-000002boundary).
Because the constraint coefficients are real, the same vector is stamped as row and column, preserving the module-wide reciprocity convention $\mathbf{K} = \mathbf{K}^{\mathsf T}$ (plain transpose — never the adjoint). Constraint rows are scaled by a nominal admittance for conditioning; the physical coupling current is coupling.scale * w.
ybus_augmented retains magnetising/excitation and supported neutral-ground branches when it promotes a transformer to winding ports. HELM consumes that matrix directly; no downstream shunt reconstruction is needed.
The holomorphic embedding
The power-flow equations are embedded in a complex parameter $s$. Voltage sources stay fixed for all $s$; loads enter through one of two embeddings:
embedding | germ ($s = 0$) | load at $s$ |
|---|---|---|
:load_scaling (default) | energized no-load network | every load part scaled by $s$ — $s$ is a load multiplier |
:impedance_germ | network loaded by equivalent admittances | constant-Z parts fixed in the matrix; other parts $(1-s)\,y_g\Delta V + s\,I_{\text{law}}(\Delta V)$ |
In both cases the germ comes from one linear solve and $s = 1$ is the actual problem. The impedance germ determines nodes that the no-load germ leaves undetermined (a star point held only by its loads); its $s$ is not a load multiplier, so the singularity estimate is then only a series diagnostic.
Load laws. A sub-load across $(p, q)$ draws $I = \sum_\gamma \kappa_\gamma |\Delta V|^\gamma / \overline{\Delta V}$ ($\gamma = 0$ constant power, $1$ constant current, $2$ constant impedance, any other exponent exponential). With the reflected series $\tilde{\Delta V}(s) = \overline{\Delta V(\bar s)}$ — holomorphic, and equal to $\overline{\Delta V}$ on the real axis — the product $m = \Delta V\,\tilde{\Delta V}$ is a holomorphic stand-in for $|\Delta V|^2$, and $|\Delta V|^\gamma = m^{\gamma/2}$ follows from J. C. P. Miller's power-series recursion. Every ZIP and exponential model is therefore inside the embedding; nothing is linearised.
Source reference. source_reference = :earth (default) fixes source phase terminals to their phasors and the source-bus neutral to 0 V, as the OPF does — a Dirichlet boundary eliminated from the unknowns. source_reference = :neutral imposes each phasor between the phase and the source neutral as a bordered constraint row (with the source current as its unknown), so the source neutral floats with the network's actual earthing — a grounding resistor at the source is honoured instead of being shorted.
Every voltage and coupling/source current is a holomorphic function of $s$, expanded as a power series whose order-$n$ coefficients solve
\[\mathbf{K}_{UU}\, \mathbf{x}[n] = \mathbf{rhs}\big(\mathbf{x}[0..n{-}1]\big)\]
— one LU factorization serves the germ and every order. The nonlinear terms use the conjugate-reflection trick with incremental inverse- and power-series convolutions; phase-to-phase and delta-connected loads come out of the same machinery (the load split is shared with ybus_linearized, so the load model is byte-equivalent to the OPF's). Constraint rows have identically zero right-hand side at every order: the linear port equations hold term-by-term. The final physical residual also checks the evaluated voltages and port currents.
The series is evaluated at $s = 1$ by Padé analytic continuation (Wynn's epsilon algorithm). Convergence is judged physically: the returned voltages are plugged back into the full nonlinear current-mismatch equations.
Convergence and singularity diagnostics
The implementation makes one positive claim: HELM_CONVERGED means the Padé-evaluated state satisfies the full nonlinear current mismatch tolerance on the no-load-connected branch. Its other statuses describe the finite series that was computed; they do not certify non-existence:
termination_status | meaning |
|---|---|
HELM_CONVERGED | the operational solution (the branch continuously connected to no-load) |
HELM_SERIES_DIVERGED | nonlinear mismatch failed and every exposed coefficient-tail norm ratio exceeds one |
HELM_MAX_ORDER | nonlinear mismatch failed without the growing-tail classification; retrying with a larger max_order may help |
The raw diagnostics are available in both APIs:
pade_spread: absolute difference between the final two Wynn-epsilon Padé estimates for every coefficient row;coefficient_tail_norms: max-norm of each final coefficient order;coefficient_tail_ratios: adjacent ratios used byHELM_SERIES_DIVERGED;singularity_estimate: Domb–Sykes extrapolation of the nearest coefficient-dominating singularity in $s$.
On a simple radial constant-power saddle-node, singularity_estimate tracks the analytic collapse multiplier. On a general network, another real or complex singularity, finite-order effects, or cancellation can dominate the coefficients. Treat it as a heuristic and validate any collapse interpretation with continuation power flow or an analytically known system. load_margin remains a compatibility alias for this value, but its old name must not be read as a guarantee.
Four-wire and n-wire modelling
Nothing is Kron-reduced: every declared (bus, terminal) is a node unless it is perfectly grounded or aliased by a closed switch or negligible-impedance line. Neutral, PE or any further conductor is an ordinary node with its own KCL row, coupled through the full $n \times n$ line impedance matrices. The recursion is generic over node indices and terminal pairs, so the solver has no conductor-count assumption — the test suite solves a 5-conductor feeder with separate N and PE and a phase-to-PE leakage load. The remaining 4-wire-specific conventions live at the data boundary, not in the solver:
- WYE loads and sources identify one neutral per bus by its label (
_neutral_terminal/_neutral_labels); a bus with two neutral-like conductors needsSINGLE_PHASEper-pair loads to choose between them. - Voltage sources are WYE phase-to-reference phasors (the BMOPF schema has no source configuration or internal impedance).
- Connection configurations (
WYE,DELTA,SINGLE_PHASE) are expanded to terminal pairs by the shared_load_subloadsdecomposition. The solver consumes only those pairs, so an explicit per-pair connection list in the data model would make HELM fully n-wire with no solver change.
Requirements and limitations
- At least one voltage source (WYE / SINGLE_PHASE; DELTA references raise an error).
- Generators and IBRs raise an
ArgumentError. The BMOPF model gives them bounds and control profiles, not fixed power-flow injections, so HELM refuses them rather than solving a network that silently omits them. - Transformer domains are validated upstream. Nominal coil voltages must be explicit, positive and finite. N-winding units need matching phase counts, supported WYE or three-phase DELTA maps, every finite pairwise impedance, and network shunts for grounding. Unsupported maps and missing terminals raise
ArgumentError.ideal_xfmrs=:stamprejects any unit requiring a border; use the default:constrainfor small/singular leakage. Thexfmr_z_min_ohmthreshold selects a representation, not a zero approximation. Above it, a poorly conditioned primitive may still limit current-residual accuracy. Redundant ideal cycles or floating references can make the germ singular even when each individual transformer is supported. - Every node needs a linear path to a reference at the germ. Islands and floating ideal deltas are diagnosed with an error naming the floating
(bus, terminal)nodes. Nodes held only by loads needembedding = :impedance_germ. - Unearthed star points with constant-power or constant-current loads are often ill-posed. Their neutral can be non-unique (balanced constant-power stars admit a continuum of displaced neutrals) or non-existent (constant current magnitudes that violate the triangle inequality cannot sum to zero). HELM then reports
HELM_SERIES_DIVERGEDwith a singularity estimate below one instead of returning one branch arbitrarily. - Time series are not applied; HELM solves the snapshot values in the network dictionary.
Tracked follow-ups remain separate: residual scaling (#64), explicit DER injections (#65), load-only star-point classification (#66), and additional OpenDSS parity decks (#67).
Validation
The test suite (test/helm_tests.jl) checks, always:
- Padé continuation against series with known limits — including series that diverge at $s = 1$ but continue analytically, and one with no limit (the spread indicator must refuse to lock in);
- a closed-form two-node feeder: voltages to
rtol 1e-9, the neutral-rise detail, andsingularity_estimateagainst the analytic saddle-node $P^* = E^2/4R$ (≈ 6.6,≈ 2, and< 1past collapse); - a warm-started natural-parameter continuation trace whose nonlinear Ipopt correctors bracket that analytic saddle-node, checked against HELM convergence and series-divergence classifications;
- switch
:alias ≡ :constrainvoltage identity with exact conductor currents; - delta and line-to-line loads against a rotated closed form;
- constant-current, exponential and full-ZIP laws against closed forms on the two-node feeder (
rtol 1e-11, both embeddings); source_reference = :neutralagainst an independent MNA solve with source and load neutral earthing resistors;- an ideal single-phase transformer whose secondary is earthed only through its neutral resistor, against a near-ideal stamped unit;
- an unearthed star point (impedance germ) and a 5-conductor N + PE feeder;
- ideal and finite center-tap, autotransformer, open-delta and n-winding ports, with finite-primitive comparisons, independent complex-power and voltage-drop checks, partially singular three-winding leakage, and retained domain refusals;
- the
ybus_linearizedresidual oracle $\lVert \mathbf{Y}\mathbf{V} - \mathbf{i}_{\text{comp}}(\mathbf{V})\rVert_\infty \approx 0$ at every returned solution (two independent code paths).
Gated on OpenDSSDirect: node-to-earth voltage parity on the pf_comparison decks (sub-mV on line/delta/capacitor/ZIP decks; a few mV through Yd/Dy transformers), and a 3-way HELM ≈ Ipopt solve_pf ≈ OpenDSS oracle.
API reference
The HELM API lists the public types, functions and result fields for this guide.