Neutral reduction reference and API
Use this transformation when the assumed neutral grounding is appropriate to the study. The power-flow and operability overview places model reduction alongside the available solution and diagnostic methods.
PowerOptLab.kron_reduce_bmopf — Function
Reduce explicit grounded neutrals in a BMOPF network.
input may be a BMOPF dictionary or JSON string. A dictionary input returns a new dictionary; a JSON input returns a dictionary unless as_json=true, in which case strict-schema JSON text is returned. Bus coordinate extensions are omitted from JSON by default; include_coordinates=true preserves them as a non-strict extension. Dictionary output retains coordinates regardless of this serialization option. The input is never mutated.
Only neutral terminals that are explicit (neutral_terminal) or use the conservative n/N convention are reduced. Series line matrices are reduced exactly by a Schur complement with the neutral voltage fixed at zero; π shunt rows/columns and conductor-indexed ratings are projected by deletion. Active neutral-leg devices (for example IBR FOUR_LEG) and ambiguous maps are rejected with an ArgumentError.
kron_reduce_bmopf(net; neutral_terminals=nothing, as_json=false, include_coordinates=false) returns a new BMOPF dictionary (or schema-valid JSON when as_json=true) and never mutates net. A JSON string is accepted as the first argument. Neutral labels come from terminal_conventions.neutral when that block is present; otherwise the conservative n/N naming convention is used. A Dict("bus_id" => "label") neutral_terminals override is available for datasets whose labels are not declared.
Dictionary output preserves bus coordinates. JSON output omits the non-spec longitude/latitude fields by default to retain the strict-schema contract. Use as_json=true, include_coordinates=true for an explicit coordinate-preserving extension; that output is not strict-schema JSON when coordinates are present. The serialization choice applies both when neutrals are reduced and when the input already has no explicit neutral; it does not change the electrical model.
For each affected line, the series impedance is reduced exactly with Zᵣ = Zₚₚ − Zₚₙ Zₙₙ⁻¹ Zₙₚ, with the explicit neutral voltage constrained to zero. Inline matrices and referenced linecodes are supported, including line lengths, line π-shunt projections, shared-linecode cloning when retained conductor orders differ, and conductor-indexed current ratings. The output removes neutral bus names and AC terminal-map entries across lines, sources, loads, generators, switches, shunts, capacitors, IBRs, and transformer windings. Grounded WYE/SINGLEPHASE capacitors become equivalent phase-to-ground shunts. Phase-to-neutral voltage bounds are intersected with phase-to-ground bounds; `vnmax` and neutral-conductor current limits are dropped with an audit entry because the neutral is now ideal ground.
| Field/family | Reduction rule | Audit or refusal |
|---|---|---|
bus.terminal_names, perfectly_grounded_terminals | Remove the resolved neutral; filter grounds by value | Classifies each bus as exact or forced-ground projection |
bus.v_min/v_max, vpn_min/vpn_max | Select terminal-indexed phase entries and intersect bounds | Contradictory intersections error; vn_max is dropped |
Line R/X_series_* | Exact Zpp − Zpn Znn⁻¹ Znp Schur complement | Stores K = −Znn⁻¹Znp, conductor maps, and neutral π-row coefficients |
Line G/B_*, shunts | Remove grounded-neutral rows/columns; neutral-only ground shunts are removed | Neutral current ratings are explicitly reported as lost |
| WYE/SINGLE_PHASE capacitors | Materialize equivalent phase-to-ground shunt | Time-varying capacitor conversion is refused |
| Loads, sources, generators, switches | Remove neutral map entries and slice only conductor-indexed vectors | Ambiguous role/order errors; phase arrays are preserved |
| IBR and transformers | Active neutral-leg IBRs and neutral-bearing transformers are refused | No invalid shortened BMOPF subtype is emitted |
DC buses, DC terminal maps, and DC grounding are intentionally outside the transformation. Structural, matrix, or bound time-series targets are refused; ordinary snapshot data remains untouched. The reduced output is BMOPF JSON schema-valid when serialized with as_json=true, include_coordinates=false; upstream 0.1.0 may still report the known WYE arity warning for a grounded WYE whose implicit midpoint is no longer listed.
The transformation is refused for singular or near-singular neutral blocks, ambiguous maps, DELTA elements containing a neutral, active IBR FOUR_LEG neutral physics, unsupported center-tap/single-phase transformer reductions, and time-varying structural/impedance data whose commutation is not proven. Matrix keys follow BMOPFTools' sparse convention: absent entries are zero, a missing reciprocal is mirrored, and explicitly stored full entries take precedence. Every reduction records original/kept conductor ordering, the neutral-current recovery vector K = −Zₙₙ⁻¹ Zₙₚ, bound rewrites, dropped constraints, and whether a bus was already perfectly grounded or was forced to ideal ground in net["_meta"]["kron_reduction"] and net["extras"]["kron_reduction"].
The package test target requires OpenDSSDirect.jl and runs an independent comparison: an explicit four-wire node-0-ground deck and its manually projected three-wire deck. It asserts convergence and compares retained phase voltages and line currents at both ends, source P/Q, total losses, and the neutral-current recovery relation Iₙ = K Iₚ against the reduced BMOPF solve. The older bundled finite-0.001-ohm grounding fixture remains useful as a near-ground comparison, but is not the test of exact equivalence.
reduced = kron_reduce_bmopf(net)
json = kron_reduce_bmopf(net; as_json=true)