HELM versus nonlinear power flow

<!– study-executable –>

Audience: power-system researchers · Scope: four-wire distribution power flow, solvability diagnostics, and cross-method validation.

The Holomorphic Embedding Load-flow Method (HELM) is not merely another nonlinear iteration. It constructs the branch connected to an energized no-load network and evaluates it by analytic continuation. This gives it useful, independent numerical evidence beside the Ipopt-based nonlinear solve_pf, but a finite-order divergent series is not a proof of voltage collapse.

The trade-off is explicit: the embedding covers the passive network and every BMOPF load law (constant power, current and impedance, ZIP, exponential). It cannot replace the nonlinear engine for IBRs, generators, controls, or OPF limits, and refuses networks that contain generators or IBRs rather than silently dropping them.

From a checkout with pinned dependencies installed, run julia --project=. scripts/run_study_tutorials.jl, or paste this page's Julia blocks into a fresh session in order. CI executes the published blocks on Julia 1.10 and current stable.

Build the teaching feeder

The data are synthetic: a 230 V source supplies a 2 kW constant-power load through phase and neutral conductors of 0.05 Ω each. Only the source neutral is grounded. This single-phase example keeps the reference calculation simple while retaining neutral displacement.

using PowerOptLab
using BMOPFTools: parse_bmopf, solve_pf, SIUnitsScaling

function resistive_feeder(; power_w=2000.0, model="constant_power")
    parse_bmopf("""
    {"bus": {
       "grid": {"terminal_names": ["1", "n"],
                "perfectly_grounded_terminals": ["n"]},
       "loadbus": {"terminal_names": ["1", "n"]}},
     "voltage_source": {
       "supply": {"bus": "grid", "terminal_map": ["1"],
                  "v_magnitude": [230.0], "v_angle": [0.0]}},
     "linecode": {"cable": {"R_series_1_1": 0.05, "R_series_2_2": 0.05}},
     "line": {"service": {"bus_from": "grid", "bus_to": "loadbus",
               "terminal_map_from": ["1", "n"], "terminal_map_to": ["1", "n"],
               "linecode": "cable", "length": 1.0}},
     "load": {"demand": {"bus": "loadbus", "terminal_map": ["1", "n"],
               "configuration": "SINGLE_PHASE", "model": "$model",
               "p_nom": [$power_w], "q_nom": [0.0], "v_nom": [230.0]}}}
    """; from_string=true)
end

net = resistive_feeder()
vbase = 230.0
loop_resistance = 0.10
load_voltage_ref = (vbase + sqrt(vbase^2 - 4loop_resistance*2000.0))/2
neutral_voltage_ref = (vbase - load_voltage_ref)/2

The high-voltage root of $U^2-230U+0.10P=0$ gives approximately 229.127 V phase-to-neutral at the load and 0.4364 V neutral-to-earth. This independent reference is conditional on the resistive, unity-power-factor circuit.

1. Two solvers, different evidence

QuestionHELM solve_pf_helmNonlinear solve_pf
Operating pointno-load germ, power series, Padé continuationiterative nonlinear feasibility/optimization solve
Initializationnonenumerical initialization and local convergence matter
Branchcontinuously connected to no-load statefeasible local point reached by the solve
Failed solveexposes Padé/coefficient diagnosticsexposes nonlinear solver status
Collapse studysingularity_estimate is a heuristicloading continuation is separate
Load/device modelall static load laws; no generators, IBRs or controlsfull engine-supported operational model

Agreement on common physics is strong cross-method evidence because the numerical mechanisms differ. Disagreement should trigger a model/branch audit, not a vote for a preferred solver.

2. HELM's non-obvious construction

HELM introduces a complex loading parameter $s$. Sources stay fixed; supported loads scale from the energized no-load germ at $s=0$ to the study case at $s=1$.

\[s=0:\ \text{energized no-load germ},\qquad s=1:\ \text{requested operating point}.\]

The germ is not a flat-voltage approximation. In an unbalanced four-wire feeder it includes the actual source boundary and no-load neutral equilibrium. Each voltage and ideal-coupling current is a holomorphic series in $s$. One LU factorization of the augmented nodal system serves every coefficient order; Wynn-epsilon Padé continuation evaluates the series at $s=1$.

using PowerOptLab

helm = helm_series(net; max_order=40, tol=1e-8)
helm.status       # :converged | :series_diverged | :max_order_reached
helm.residual     # full nonlinear current mismatch [A]
helm.pade_spread  # last-two Padé differences for every coefficient row
helm.coefficient_tail_ratios
helm.singularity_estimate # heuristic; validate before calling it a margin
@assert helm.status == :converged
@assert helm.residual < 1e-7
@assert abs(helm.V[("loadbus", "1")] - helm.V[("loadbus", "n")] - load_voltage_ref) < 1e-5
@assert abs(helm.V[("loadbus", "n")] - neutral_voltage_ref) < 1e-5

The final test is physical: returned voltages are substituted into the full nonlinear current mismatch. solve_pf_helm returns the standard result shape.

Why this is more than avoiding an initial guess

Iterative solvers can fail because of scaling, a local basin, line search, or a poor start. HELM fixes the studied branch by continuation from no load and therefore supplies different evidence. Persistent finite-order coefficient growth at $s=1$ says this series evaluation did not resolve the requested state; another study is required before concluding that the solvable branch ends there.

3. Interpret status and margin precisely

StatusMeaningResponse
HELM_CONVERGEDoperational branch reached; physical residual met toleranceinspect voltage/diagnostics and compare with nonlinear PF
HELM_SERIES_DIVERGEDmismatch failed and the exposed coefficient tail growsinspect Padé spread/ratios and run a loading continuation or analytic check
HELM_MAX_ORDERmismatch failed without the growing-tail classificationincrease max_order; the result is inconclusive

Coefficient-tail Domb-Sykes extrapolation estimates a coefficient-dominating singularity $\lambda$. On the repository's analytic two-node saddle-node, a value near 2 means the present load is about half the known collapse loading, and a value below 1 agrees with the known branch ending before $s=1$. General networks may have other real or complex singularities, so this interpretation does not transfer automatically. NaN means the finite tail could not produce an estimate.

Pitfall: calling every failed solve voltage collapse

Both HELM_SERIES_DIVERGED and HELM_MAX_ORDER are inconclusive about non-existence. Likewise, failure of nonlinear solve_pf is not proof. For a defensible collapse claim, bracket the limit with continuation power flow or use an analytically known fixture, and report the common model and tolerances.

4. Four-wire and ideal-element strengths

HELM uses an augmented four-wire nodal system. Floating neutrals remain nodes, so neutral displacement is solved rather than silently grounded. Zero-impedance switches and ideal transformers are bordered constraints, not arbitrary huge admittances:

\[\begin{bmatrix}Y&A^T\\A&0\end{bmatrix} \begin{bmatrix}V\\w\end{bmatrix}= \begin{bmatrix}I\\0\end{bmatrix}.\]

Their voltage identities hold term-by-term. With switches=:constrain, HELM also returns physical switch-conductor currents; :alias gives identical voltages via node fusion.

hr = helm_series(net; switches=:constrain, ideal_xfmrs=:constrain)
hr.couplings
@assert hr.converged
@assert isempty(hr.couplings)  # This fixture has no switches or transformers.

Pitfall: using a huge admittance for an ideal element

An arbitrary 1/z changes conditioning and adds a fictitious voltage drop. Bordered constraints retain exact identities. Note that a transformer promoted to an ideal coupling is purely ideal: its magnetizing shunt and neutral-ground branch are absent. That modelling choice must match the comparison case.

5. HELM as an independent oracle

For a case inside both solvers' scope, compare conductor voltages and currents:

using BMOPFTools: solve_pf

h = solve_pf_helm(net)
n = solve_pf(net; per_unit=false)
@assert h["termination_status"] == "HELM_CONVERGED"
@assert n["termination_status"] in ("LOCALLY_SOLVED", "OPTIMAL")
Δv = h["bus"]["loadbus"]["1"]["vm"] - n["bus"]["loadbus"]["1"]["vm"]
@assert abs(Δv) < 1e-5
n_phase = complex(n["bus"]["loadbus"]["1"]["vr"], n["bus"]["loadbus"]["1"]["vi"])
n_neutral = complex(n["bus"]["loadbus"]["n"]["vr"], n["bus"]["loadbus"]["n"]["vi"])
@assert abs(n_phase - n_neutral - load_voltage_ref) < 1e-5
@assert abs(n_neutral - neutral_voltage_ref) < 1e-5
println("HELM / nonlinear PF: load voltage = ", round(load_voltage_ref; digits=4),
        " V; neutral rise = ", round(neutral_voltage_ref; digits=4), " V")

Repository validation combines closed-form feeders, a separate ybus_linearized current-mismatch oracle, OpenDSS decks, and three-way HELM-Ipopt-OpenDSS comparisons. A good research workflow is:

  1. Specify common source, grounding, switch/transformer, and load physics.
  2. Compare phase-to-earth voltages, neutral rise, and relevant currents.
  3. Inspect residuals, Padé spreads, coefficient-tail ratios, and the singularity estimate.
  4. Investigate disagreement before changing tolerances.
  5. Add operational physics only to nonlinear PF, clearly marking HELM's scope.

Pitfall: comparing different physics

HELM cannot validate nonlinear PF when the latter includes generators, IBR controls, or operational limits absent from HELM. Reduce to the common supported model first; otherwise the discrepancy is expected model mismatch, not solver evidence.

6. Voltage-dependent loads stay holomorphic

Constant-current ZIP fractions and exponential loads involve $|\Delta V|$, which is not holomorphic in $\Delta V$ alone. HELM pairs each voltage series with its conjugate reflection $\tilde{\Delta V}(s) = \overline{\Delta V(\bar s)}$, which is holomorphic and agrees with $\overline{\Delta V}$ for real $s$. Their product $m(s) = \Delta V(s)\,\tilde{\Delta V}(s)$ equals $|\Delta V|^2$ on the real axis and is holomorphic, so $|\Delta V|^\gamma = m^{\gamma/2}$ has its own power series. The order-$n$ recursion still needs only lower-order coefficients. For a constant-current load on this feeder, $P(U) = P_0 U / 230$, so the phase-to-neutral load voltage is exactly $U = 230 - 0.10\,P_0/230$:

net_with_constant_current = resistive_feeder(model="constant_current")
current_helm = helm_series(net_with_constant_current)
current_ref = vbase - loop_resistance * 2000.0 / vbase
@assert current_helm.status == :converged
@assert abs(current_helm.V[("loadbus", "1")] -
            current_helm.V[("loadbus", "n")] - current_ref) < 1e-9

HELM needs an energized WYE/SINGLEPHASE source. With the default `embedding = :loadscaling, every node also needs a linear path to a reference at the no-load germ.embedding = :impedance_germ` represents the loads by equivalent admittances at the germ, which is enough for nodes held only by loads, such as an unearthed star point. Generators and IBRs raise an error, because their set-points are OPF variables or control-law outputs in the BMOPF model. Use nonlinear PF for operational devices and controls.

Pitfall: treating rejection as a numerical weakness

The generator/IBR rejection protects the embedding's mathematical scope. Solving a network with those devices silently removed would be a different model with interpretable-looking diagnostics. An explicit scope is more scientifically useful than silently solving a different model.

7. Publication checklist

Report the load representation, source/reference and neutral treatment, ideal-element model, HELM order/tolerance/status/residual, Padé/coefficient diagnostics, singularity estimate, and cross-solver comparison on common physics. State every excluded control and unsupported load component. HELM's value is not replacing nonlinear PF: it provides a deterministic analytic-continuation reference whose claims can be checked independently.

For API details see HELM power flow.