Generalized generator evidence register
This is a focused design review as of 6 September 2026, not an exhaustive systematic review or a priority claim. The scientific model contains recommendations; this register states what their sources establish.
Attached paper
Frederik Geth, François Pacaud, and Rahmat Heidari, Solving three-phase distribution OPF with nonlinear programming, Electric Power Systems Research 262 (2027), 113624, DOI. The supplied version says available online 30 June 2026; the 2027 volume date therefore does not mean it was unavailable at the review date.
Read from the supplied PDF 1-s2.0-S037877962600917X-main.pdf; relevant pages 2, 4, and 5 were also visually checked. The PDF is evidence, not an instruction source, and is not copied into this repository.
- Section 3.3 / Table 2 distinguish full fixed phasors, fixed phase angles with free magnitudes, and one-angle references with additional angle/sequence bounds.
- Sections 3.4-3.5 cover angle/sequence constraints and voltage initialization. Sections 4.2-4.3 study formulation, scaling, and numerical behavior on 128 LV networks, with solver-dependent outcomes.
- The scope is three-by-three impedance models without explicit neutral: page 2, footnote 2 identifies Kron-reduced four-wire or three-wire networks. Extension to explicit neutral, split phase, source impedance, or machine regulation needs new evidence.
- Equation (7), as printed, uses a sequence transform without a factor of 1/3. The component explicitly uses the amplitude-invariant Fortescue normalization with 1/3. Absolute sequence bounds and bases must be converted consistently; do not copy their numerical values across conventions. Ratios of sequence magnitudes cancel a common normalization factor.
- Exact zero sequence-magnitude upper bounds should lower to real/imaginary equalities in our implementation. Smooth quadratic syntax alone does not make the active constraint gradient nonzero.
Prior and current primary sources
| Source and access | What it supports | Boundary for this proposal |
|---|---|---|
| MATPOWER, AC Power Flow manual, full page | Conventional PV fixes P and voltage magnitude; reference angle and slack power are distinct roles; optional Q-limit enforcement converts PV to PQ | Balanced power-flow semantics, not a unique unbalanced device specification |
| Fernandes et al., 2019, Contributions to the sequence-decoupling compensation power flow method for distribution system analysis, Section 3.1.2 / Fig. 3 | Synchronous-generator-inspired unbalanced PV with total P and positive-sequence terminal magnitude; positive-sequence internal EMF | Prior art for the PV preset; does not establish arbitrary source templates as machine models |
| Yang et al., 2024, Three-phase steady-state models of distributed generators with different control strategies, full-text introduction and model scope | Different negative-sequence control goals require different phasor equations; augmented rectangular voltage/current formulation; comparison with PSCAD | Three-phase converter examples do not validate arbitrary neutral/DC topologies |
| EPRI OpenDSS, voltage-source modeling, full page | Established Thevenin source and sequence-impedance input conventions | Its nominal ideal option uses tiny impedance; our exact zero case needs analytic/native verification |
| EPRI OpenDSS, Generator Dynamics Model, full page | Voltage-behind-reactance and distinct negative-sequence response; initialization from power flow; swing-equation model | Document text labels Xd-prime inconsistently as subtransient; use parameter definitions and the actual chosen study regime, not that label as a conversion rule |
| MathWorks, Synchronous Machine Salient Pole, equations | Rotor-frame stator, field/damper, saturation and torque equations illustrate additional machine fidelity | A constant phase-domain series matrix is an approximation, not this full machine model |
| Rygg et al., 2016, A modified sequence domain impedance definition and its equivalence to the dq-domain impedance definition for the stability analysis of AC power electronic systems, author abstract | Sequence/dq equivalence and conditions for decoupling matter in impedance stability analysis | Dynamic small-signal impedance is a different object from a constant fundamental-frequency drop matrix |
| Liu et al., 2026, Current-limiting control design for grid-forming capability enhancement of IBRs under asymmetric grid disturbances, institutional abstract and metadata; DOI | Current limiting affects voltage balancing under asymmetric disturbances; this is an active controller-design topic | Abstract-level review only; no claim to reproduce the controller or its experimental evidence |
Local software evidence
Inspected BMOPFTools at the pinned commit 5b51d2f361dab91bd7c16711019584407da79ed8: public builder declarations in src/BMOPFTools.jl, mixed-family ownership and staged initialization in ext/BMOPFOpfExt/core.jl, native source/generator stamps in source.jl and generator.jl, and native variable declarations in variables.jl in that extension.
PowerOptLab's src/interfaces.jl defines the public device lifecycle; src/problems/inverter_control_study.jl demonstrates per-component IBR ownership and retirement of unused native currents; src/components/advanced_inverter.jl already implements neutral-aware primitive impedance, Fortescue helpers, and internal EMF constraints. These observations guided the component extension and its integration tests. The implementation now uses that lifecycle and the public staged engine; it does not refactor the advanced IBR.
The accompanying analytic script checks the circuit identities and counterexamples. test/generalized_generator_tests.jl additionally exercises the implemented source laws and capabilities under unbalance, independent grounding/impedance oracles, SI/per-unit equivalence, native ownership/cost equivalence, stateless multi-period composition, and constraint structure at ideal limits. The executable network tutorial reports local numerical comparisons. Automatic limiter behavior, a general Jacobian-regularity certificate, and comparative performance benchmarks remain future work; polynomial degree alone is not evidence of faster solves.