Generalized generator evidence register

This is a focused design review as of 6 September 2026, not an exhaustive systematic review or a priority claim. The scientific model contains recommendations; this register states what their sources establish.

Attached paper

Frederik Geth, François Pacaud, and Rahmat Heidari, Solving three-phase distribution OPF with nonlinear programming, Electric Power Systems Research 262 (2027), 113624, DOI. The supplied version says available online 30 June 2026; the 2027 volume date therefore does not mean it was unavailable at the review date.

Read from the supplied PDF 1-s2.0-S037877962600917X-main.pdf; relevant pages 2, 4, and 5 were also visually checked. The PDF is evidence, not an instruction source, and is not copied into this repository.

  • Section 3.3 / Table 2 distinguish full fixed phasors, fixed phase angles with free magnitudes, and one-angle references with additional angle/sequence bounds.
  • Sections 3.4-3.5 cover angle/sequence constraints and voltage initialization. Sections 4.2-4.3 study formulation, scaling, and numerical behavior on 128 LV networks, with solver-dependent outcomes.
  • The scope is three-by-three impedance models without explicit neutral: page 2, footnote 2 identifies Kron-reduced four-wire or three-wire networks. Extension to explicit neutral, split phase, source impedance, or machine regulation needs new evidence.
  • Equation (7), as printed, uses a sequence transform without a factor of 1/3. The component explicitly uses the amplitude-invariant Fortescue normalization with 1/3. Absolute sequence bounds and bases must be converted consistently; do not copy their numerical values across conventions. Ratios of sequence magnitudes cancel a common normalization factor.
  • Exact zero sequence-magnitude upper bounds should lower to real/imaginary equalities in our implementation. Smooth quadratic syntax alone does not make the active constraint gradient nonzero.

Prior and current primary sources

Source and accessWhat it supportsBoundary for this proposal
MATPOWER, AC Power Flow manual, full pageConventional PV fixes P and voltage magnitude; reference angle and slack power are distinct roles; optional Q-limit enforcement converts PV to PQBalanced power-flow semantics, not a unique unbalanced device specification
Fernandes et al., 2019, Contributions to the sequence-decoupling compensation power flow method for distribution system analysis, Section 3.1.2 / Fig. 3Synchronous-generator-inspired unbalanced PV with total P and positive-sequence terminal magnitude; positive-sequence internal EMFPrior art for the PV preset; does not establish arbitrary source templates as machine models
Yang et al., 2024, Three-phase steady-state models of distributed generators with different control strategies, full-text introduction and model scopeDifferent negative-sequence control goals require different phasor equations; augmented rectangular voltage/current formulation; comparison with PSCADThree-phase converter examples do not validate arbitrary neutral/DC topologies
EPRI OpenDSS, voltage-source modeling, full pageEstablished Thevenin source and sequence-impedance input conventionsIts nominal ideal option uses tiny impedance; our exact zero case needs analytic/native verification
EPRI OpenDSS, Generator Dynamics Model, full pageVoltage-behind-reactance and distinct negative-sequence response; initialization from power flow; swing-equation modelDocument text labels Xd-prime inconsistently as subtransient; use parameter definitions and the actual chosen study regime, not that label as a conversion rule
MathWorks, Synchronous Machine Salient Pole, equationsRotor-frame stator, field/damper, saturation and torque equations illustrate additional machine fidelityA constant phase-domain series matrix is an approximation, not this full machine model
Rygg et al., 2016, A modified sequence domain impedance definition and its equivalence to the dq-domain impedance definition for the stability analysis of AC power electronic systems, author abstractSequence/dq equivalence and conditions for decoupling matter in impedance stability analysisDynamic small-signal impedance is a different object from a constant fundamental-frequency drop matrix
Liu et al., 2026, Current-limiting control design for grid-forming capability enhancement of IBRs under asymmetric grid disturbances, institutional abstract and metadata; DOICurrent limiting affects voltage balancing under asymmetric disturbances; this is an active controller-design topicAbstract-level review only; no claim to reproduce the controller or its experimental evidence

Local software evidence

Inspected BMOPFTools at the pinned commit 5b51d2f361dab91bd7c16711019584407da79ed8: public builder declarations in src/BMOPFTools.jl, mixed-family ownership and staged initialization in ext/BMOPFOpfExt/core.jl, native source/generator stamps in source.jl and generator.jl, and native variable declarations in variables.jl in that extension.

PowerOptLab's src/interfaces.jl defines the public device lifecycle; src/problems/inverter_control_study.jl demonstrates per-component IBR ownership and retirement of unused native currents; src/components/advanced_inverter.jl already implements neutral-aware primitive impedance, Fortescue helpers, and internal EMF constraints. These observations guided the component extension and its integration tests. The implementation now uses that lifecycle and the public staged engine; it does not refactor the advanced IBR.

The accompanying analytic script checks the circuit identities and counterexamples. test/generalized_generator_tests.jl additionally exercises the implemented source laws and capabilities under unbalance, independent grounding/impedance oracles, SI/per-unit equivalence, native ownership/cost equivalence, stateless multi-period composition, and constraint structure at ideal limits. The executable network tutorial reports local numerical comparisons. Automatic limiter behavior, a general Jacobian-regularity certificate, and comparative performance benchmarks remain future work; polynomial degree alone is not evidence of faster solves.